TM 5-3610-293-13&P
4-27. PHASE MONITOR METER. - Continued
(3) Remove nuts (6) and voltage meter (7).
(4) Position replacement voltage meter (7) and secure with nuts (6).
(5) Connect wires (5) and remove tags.
(6) Attach phase monitor meter (1) to shelter wall by securing flat washers (4), lockwashers (3), and
screws (2).
(7) Turn on power and test operation.
b.
Repair by replacing fuse holder.
WARNING
The main power cable to the Press Section MUST be disconnected before
performing any maintenance on the phase monitor meter. Failure to do so may
result in DEATH or serious injury.
(1) Remove phase monitor meter (1) from wall by removing screws (2), lockwashers (3) and flat
washers (4).
(2) Tag and unsolder wires (8).
(3) Remove nut (9) and fuse holder (10).
(4) Position replacement fuse holder (10) and secure with nut (9).
(5) Solder wires (8) and remove tags.
(6) Attach phase monitor meter (1) to shelter wall by securing flat washers (4), lockwashers (3), and
screws (2).
(7) Turn on power and test operation.
4-84