TM 5-3610-295-13&P-25-12. MAIN POWER SERVICE ASSEMBLY.This task covers: a.Inspect b.RepairINITIAL SETUPToolsElectrical equipment tool kitMaterialsNonea.Inspect. (See Figure 5-4.)(1)Inspect main power service box assembly of curbside of rear wall for dents, corrosion, and security ofmounting.(2)Inspect door and hinge on main power service box assembly for ease of movement, complete closure,proper latching, and legible circuit decals.(3)Inspect circuit breaker aperture blanks for presence and security of mounting.(4)Inspect circuit breakers for proper operation and security of mounting.WARNINGDEATH or serious injury could result if electrical precautions are not taken whenmaintaining this equipment. Be sure that power cables are unplugged/disconnected, that circuit breakers are set to OFF, and that generator cables areunplugged/disconnected. Be sure the equipment is properly grounded. Alwayshave another person standing by who is familiar with electrical shock first aid.5-16