TM 5-3610-294-13&P
4-24. PHASE MONITOR METER. - Continued
(3)
Remove nuts (6) and voltage meter (7).
(4)
Position replacement voltage meter (7) and secure with nuts (6).
(5)
Connect wires (5) and remove tags.
(6)
Attach phase monitor meter (1) to shelter wall by securing flat washers (4), lockwashers (3), and
screws (2).
(7)
Turn on power and test operation.
b.
Repair by replacing fuse holder.
(1)
Remove phase monitor meter (1) from wall by removing screws (2), lockwashers (3) and flat
washers (4).
(2)
Tag and unsolder wires (8).
(3)
Remove nut (9) and fuse holder (10).
(4)
Position replacement fuse holder (10) and secure with nut (9).
(5)
Solder wires (8) and remove tags.
(6)
Attach phase monitor meter (1) to shelter wall by securing flat washers (4), lockwashers (3), and
screws (2).
(7)
Turn on power and test operation.
c.
Repair by replacing correct/incorrect phase indicator lights.
NOTE
The procedure is the same for both phase indicator lights.
(1)
Remove phase monitor meter (1) from wall by removing screws (2), lockwashers (3) and flat
washers (4).
(2)
Tag and unsolder wires (11).
(3)
Remove nut (12) and phase indicator light (13).
4-60