TM 5-3610-294-13&P
4-24. PHASE MONITOR METER. - Continued
c.
Repair by replacing correct/incorrect phase indicator lights. - Continued
(4)
Position replacement phase indicator light (13) and secure with nut (12).
(5)
Solder wires (11) and remove tags.
(6)
Attach phase monitor meter (1) to shelter wall by securing flat washers (4), lockwashers (3), and
screws (2).
(7)
Turn on power and test operation.
d.
Repair by replacing phase test switch.
(1)
Remove phase monitor meter (1) from wall by removing screws (2), lockwashers (3) and flat
washers (4).
(2)
Tag and unsolder wires (14).
(3)
Remove nut (15), lockwasher (16), and phase test switch (17).
(4)
Position replacement phase test switch (17) and secure with lockwasher (16) and nut (15).
(5)
Solder wires (14) and remove tags.
(6)
Attach phase monitor meter (1) to shelter wall by securing flat washers (4), lockwashers (3), and
screws (2).
(7)
Turn on power and test operation.
e.
Repair by replacing frequency meter.
(1)
Remove phase monitor meter (1) from wall by removing screws (2), lockwashers (3) and flat
washers (4).
(2)
Tag and disconnect wires (18).
(3)
Remove nuts (19), lockwashers (20), screws (21), and frequency meter (22).
(4)
Position replacement frequency meter (22) and secure with screws (21), lockwashers (20), and
nuts (19).
(5)
Connect wires (18) and remove tags.
(6)
Attach phase monitor meter (1) to shelter wall by securing flat washers (4), lockwashers (3), and
screws (2).
4-61