TM 5-3610-294-13&P
3-6. GENERAL. - Continued
Table 3-1. Operator Troubleshooting - Cont.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
7.
POWER DISTRIBUTION PANEL DOES NOT OPERATE.
Step 1.
Check to make sure power cable is connected and power is on.
Request Module C supervisor connect power cable and turn on power.
Step 2.
Check circuit breakers to make sure they are on.
Turn switches on.
8.
AIR CONDITIONER UNITS (24,000 AND 36,000 BTUH) DO NOT OPERATE.
Step 1.
Verify that AC circuit breaker is on at the power distribution panel.
Turn circuit breaker ON.
Step 2.
Check thermostat for proper temperature setting and heat/cool switch setting for COOL or HEAT.
Set heat/cool switch on thermostat to desired setting (HEAT or COOL) and adjust temperature set point
lever.
Step 3.
Check heat access doors on cargo door vent assemblies.
Open air conditioner vents.
Step 4.
Verify that AC dampers are open.
Open AC dampers.
3-8