TM 5-3610-295-13&P-1
4-24.
WATER TANK AND MOUNTING ASSEMBLY. - Continued
b. Repair. - Continued
CAUTION
RTV is used to secure drain petcock (10) to drain hole in shelter. Loosen RTV around the drain
petcock (10) before removing water tank (4) to prevent damage to drain petcock (10).
(d) Remove bolts (5), lockwashers (6), flat washers (7), and water tank (4).
(e) Remove water heater (8), fittings (9) and drain petcock (10).
NOTE
If necessary to replace water heater, complete steps (f) - (m).
(f) Remove screws (11) and cover (12).
(g) Tag wires (13). Remove screws (14) and disconnect wires (13).
(h) Remove nut (15) and conduit clamp (16).
(i) Loosen screws (17) and remove conduit clamp (16) from wires (13).
(j) Install clamp (16) on replacement water heater (8) by securing nut (15).
(k) Install wires (13) through conduit clamp (16) and tighten screws (17).
(l) Connect wires (13) and secure with screws (14). Remove tags.
(m) Install cover (12) and secure with screws (11).
(n) Apply RTV sealant (4, Appendix E) to pipe threads of drain petcock (10), fittings (9) and water heater (8)
and install in replacement water tank (4).
(o) Install water tank (4) and secure with flat washers (7), lockwashers (6) and bolts (5).
(p) Install tubing (3) and secure with clamps (2).
4-61